• Talk to an Expert
  • +91 9830605707

AGNI Analogue Addressable Fire Alarm System, Model – Analog Addressable Control Panel

Categories:

Description:  PICTURE a fire panel that is touchscreen-controlled, a breeze to install, provides clear and constant feedback on all aspects of fire alarm system activity and is fully compliant with EN54 parts 2, 4 & 13. Picture ENVISION – a powerful, intuitive and feature-rich range of 2 to 8 loop analogue addressable fire panels from Context Plus.

  • Designed to comply with the latest versions of EN54 parts 2, 4 and 13
  • Communication protocol – Apollo XP95/Discovery
  • Three cabinet sizes – standard (2 or 4 loops), medium (2, 4, 6 or 8 loops) and large
  • (2, 4, 6 or 8 loops)
  •  3A or 5A full EN54-4/A2 PSU and battery charger included
  • Onboard mini-USB connection to connect a PC running programming software
  • Two RS 232 ports – one dedicated to a 40 column thermal printer (optional),
  • one for ancillary devices such as ESPA protocol alphanumeric pagers / DECT
  • telephone systems
  •  4.3 inch, 472 x 248 pixel, 24 Bit, 16 M color, resistive LCD touchscreen (larger
  • touchscreen available to special order)
  • 40 characters of custom text per device
  •  Separate distinct LEDs for mandatory EN54 indications plus programmable LEDs
  • Real time clock with built in and automatic daylight saving time/backup PSU
  •  Standard upload download software includes facility to upload company logos – even
  • from a simple .jpg file from a camera
  • Secure fault tolerant network as standard (needs separate network driver PCB)
  •  Full on-screen QWERTY keyboard
  •  Day/night sensitivity
  •  Three access levels – general, authorized user and engineer
  •  Four programmable 1A sounder circuits (3A max total)
  • Directly connects to DIN standard fireman’s Interface (IFAM-FAT/FBF).
  • Interface for Key box units and ATU.
  •  Up to 200 separate LEDs per panel, programmable as Fire Zonal LEDs or other
  • Up to 64 eight loop peer to peer panel network capacity (max. distance between
  • each ‘node’ = 1KM)
  • Fault tolerant network drivers (Hi-Net)
  •  Flush and surface ‘Compact Controllers’
  • Up to 10,000 programmable and indictable system zones
  •  Greater than 100,000 addressable device system capacity
  •  20,000 event memory of all fire and fault and system events – all filterable
  •  Selectable Language
  •  ‘Slide In’ label system on custom molded bezels for customizable language
  • labels/custom description of zones and programmable LEDs. Common word processor
  • templates available with software
  •  Isolated internal/external RS485 peripheral bus for connection of ancillary
  • peripheral PCBs (15 PCBs max per panel)
  •  Up to 16 GB (2 GB as standard) internal SD card memory (removable micro SD card).
  • SD card can be programmed off site if required
  • Dedicated port for Ethernet connection (requires plug on TCP/IP PCB) to allow for
  • Internet control and monitoring
  •  Onboard printer option
  •  Modular Construction
  •  Up to 18 Ah batteries in standard cabinet, up to 38 Ah in larger cabinets